Standard total heat recovery model for water circulation conditions Water Cooled Scroll Chiller
Specifications
QR/QV standard model for water circulation conditions
Basic modules | EKWD021CRQR/QV | EKWD032CRQR/QV | EKWD043CRQR/QV | |||
Water Circulation Mode |
Nominal Cooling Capacity | kW | 74 | 110 | 150 | |
Nominal Heating Capacity | kW | 89 | 148 | 200 | ||
Total Power of Nominal Cooling Capacity | kW | 14.0 | 22.3 | 30.0 | ||
Total Power of Nominal Heating Capacity | kW | 17.2 | 28.5 | 37.4 | ||
Water flow | Application side | m³/h | 12.7 | 18.9 | 25.8 | |
Heat source side | m³/h | 15.1 | 22.8 | 30.9 | ||
Heat Recovery Mode |
Nominal Cooling Capacity | kW | 66 | 100 | 135.5 | |
Nominal Heat Recovery Capacity | kW | 83 | 126 | 170 | ||
Total Nominal Power | kW | 17 | 26 | 34.5 | ||
Nominal water flow at the heat recovery side | m³/h | 14.3 | 21.7 | 29.2 | ||
Nominal water flow at the evaporation side | m³/h | 12.7 | 18.9 | 25.8 | ||
Water heater mode | Nominal Heating Capacity | kW | 81 | 135 | 184 | |
Total Nominal Power | kW | 19.1 | 32.1 | 43.5 | ||
Nominal water flow at the hot water side | m³/h | 14.3 | 21.7 | 29.2 | ||
Water flow at the heat source side (evaporation side) |
m³/h | 15.1 | 22.8 | 30.9 | ||
Water pressure drop |
Application side (air conditioner side) | kPa | 21 | 30 | 30 | |
Heat source side | kPa | 17 | 19 | 19 | ||
Heat exchanger type |
Application side (evaporator) | Plate | Shell-and-tube | |||
Heat source side (condenser) | Shell-and-tube | |||||
Recommended total pipe diameter |
Evaporator | mm | DN65 | DN65 | DN80 | |
Condenser | mm | DN65 | DN65 | DN80 | ||
Volume Adjustment | Steps | 2 | 3 | 4 | ||
Regulation mode | Fuzzy control | |||||
Compressor | Model | Fully hermetic volute | ||||
Lubricant | Mineral oil (SUNISO 3GS) | |||||
Refrigerant | Flow control method | Electronic expansion valve | ||||
Category | R22 | |||||
Dimensions | L x H x W | mm | 1647x1202x632 | 2247x1488x710 | ||
Unit weight | Net weight | kg | 452(517) | 703(818) | 887(1040) | |
Transportation weight | kg | 478(543) | 738(853) | 922(1075) |
1, The modular water source/geothermal unit supports applications in all conditions and can switch between multiple modes to fully meet user needs for cooling, heating, and hot water. With an innovative water system, the energy-saving unit delivers an EER as high as 5.7, provides higher energy efficiency when working at a partial workload, and saves energy by 50% compared with other systems after operation in a year.
2, The unit is designed with a comprehensive water system and consists of efficient components carefully selected and designed for a low operation noise. The unit supports fuzzy volume regulation for a narrow range of temperature changes and quickly reaches the set temperature. In addition, the unit provides hot water at a set temperature as high as 55°C quickly and steadily to meet requirements for comfortable hot water in all places..
3 With modular design, the unit starts step by step, reducing the shock on the grid, and maintenance of a single unit does not affect running of other units. In addition, the unit provides multiple built-in security protection functions, and supports intelligent and centralized control, facilitating daily management.
4, The leading-edge shell design allows the unit to be installed in an outdoor space su
EuroKlimat Air Conditioning Refrigeration Company [China (Mainland)]
Business Type:Manufacturer
City: Dongguan
Province/State: Guangdong
Country/Region: China (Mainland)