EuroKlimat Air Conditioning Refrigeration Company
|
Gold Index: 9440
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Two pipe 2 rows ceiling concealed fan coil unit ESP 35 pa
Specifications
Model Performance |
EKCW 200AT |
EKCW 300AT |
EKCW 400AT |
EKCW 500AT |
EKCW 600AT |
EKCW 800AT |
EKCW 1000AT |
EKCW 1200AT |
EKCW 1400AT |
||
Rated air flow (m3/h; under static pressure of 12 Pa, 30 Pa, and 50 Pa) |
H | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 | |
M | 279 | 418 | 558 | 697 | 836 | 1115 | 1394 | 1673 | 1952 | ||
L | 170 | 255 | 340 | 425 | 510 | 680 | 850 | 1020 | 1190 | ||
Rated cooling capacity (W) | Total heating/cooling capacity | H | 1770 | 2955 | 3920 | 4635 | 5115 | 7610 | 8680 | 10495 | 11620 |
Sensible heating/cooling capacity | H | 1140 | 1980 | 2570 | 3205 | 3735 | 5535 | 6680 | 7765 | 8955 | |
Rated heating capacity (W) | H | 3280 | 5120 | 6450 | 7560 | 9095 | 12830 | 15865 | 18485 | 20770 | |
Rated input power (W) | Static pressure of 12 Pa | H | 32 | 46 | 56 | 73 | 93 | 133 | 164 | 188 | 229 |
Static pressure of 30 Pa | H | 39 | 53 | 72 | 86 | 107 | 142 | 183 | 217 | 239 | |
Static pressure of 50 Pa | H | 46 | 65 | 77 | 90 | 115 | 162 | 187 | 227 | 279 | |
Working current (A) | Static pressure of 12 Pa | H | 0.15 | 0.21 | 0.26 | 0.33 | 0.42 | 0.61 | 0.74 | 0.85 | 1.04 |
Static pressure of 30 Pa | H | 0.18 | 0.24 | 0.33 | 0.39 | 0.48 | 0.65 | 0.83 | 0.99 | 1.09 | |
Static pressure of 50 Pa | H | 0.21 | 0.29 | 0.35 | 0.41 | 0.52 | 0.74 | 0.85 | 1.03 | 1.27 | |
Sound dB(A) | Static pressure of 12 Pa | H | 34.5 | 34.5 | 37.5 | 41.0 | 45.0 | 44.5 | 48.0 | 49.0 | 52.0 |
Static pressure of 30 Pa | H | 37.0 | 40.0 | 42.5 | 44.0 | 45.5 | 46.5 | 49.5 | 49.5 | 53.0 | |
Static pressure of 50 Pa | H | 41.0 | 43.0 | 45.0 | 46.0 | 47.5 | 48.0 | 50.0 | 51.0 | 53.5 | |
Water flow (m3/h) | 0.32 | 0.51 | 0.67 | 0.80 | 0.88 | 1.31 | 1.47 | 1.81 | 2.01 | ||
Water resistance (cooling) (kPa) | 5 | 14 | 26 | 36 | 18 | 40 | 28 | 40 | 34 | ||
Water resistance (heating) (kPa) | 4 | 12 | 21 | 30 | 14 | 34 | 23 | 34 | 28 | ||
Coil | Type | Mechanically expanded quality copper tubes specially designed for air conditioners with shutter-type hyperbolic aluminum fins | |||||||||
Working pressure | 1.6MPa | ||||||||||
Test pressure | Airtightness test under pressurized water: 3.3 MPa | ||||||||||
Fan | Type | Forward-pitched multi-wing centrifugal fan with double-suction impellers made from zinc-plated steel plates | |||||||||
Related Search
Fan Coil Unit
Vertical Fan Coil Unit
Conditioning Unit
Air Conditioning
Pa Ceiling Speaker
Car Air Conditioning
More>>
Find more related products in following catalogs on Hisupplier.comCompany InfoEuroKlimat Air Conditioning Refrigeration Company [China (Mainland)]
Business Type:Manufacturer You May Like:
Printable Page
Bookmark this page
Sitemap XML About HiSupplier Help Center Customer Service Friend Links Site Map Archives Browse by: China Suppliers - Hot Products - Products Directory - Offers Directory - Suppliers Directory - Buyers Directory Language Option: العربية - Nederlands- Français- Deutsch- Italiano- 日本語- 한국의- Português- Pусский- Español Copyright © HiSupplier.com Online Inc. All Rights Reserved.
|