Model No.: EKCW-A

 
 
Two pipe 2 rows ceiling concealed fan coil unit  ESP 35 pa
 
 

 

 

Two pipe 2 rows ceiling concealed fan coil unit  ESP 35 pa

 

 

Specifications

 

Model
Performance
EKCW
200AT
EKCW
300AT
EKCW
400AT
EKCW
500AT
EKCW
600AT
EKCW
800AT
EKCW
1000AT
EKCW
1200AT
EKCW
1400AT
Rated air flow (m3/h; under static pressure of 12
Pa, 30 Pa, and 50 Pa)
H 340 510 680 850 1020 1360 1700 2040 2380
M 279 418 558 697 836 1115 1394 1673 1952
L 170 255 340 425 510 680 850 1020 1190
Rated cooling capacity (W) Total heating/cooling capacity H 1770 2955 3920 4635 5115 7610 8680 10495 11620
Sensible heating/cooling capacity H 1140 1980 2570 3205 3735 5535 6680 7765 8955
Rated heating capacity (W) H 3280 5120 6450 7560 9095 12830 15865 18485 20770
Rated input power (W) Static pressure of 12 Pa H 32 46 56 73 93 133 164 188 229
Static pressure of 30 Pa H 39 53 72 86 107 142 183 217 239
Static pressure of 50 Pa H 46 65 77 90 115 162 187 227 279
Working current (A) Static pressure of 12 Pa H 0.15 0.21 0.26 0.33 0.42 0.61 0.74 0.85 1.04
Static pressure of 30 Pa H 0.18 0.24 0.33 0.39 0.48 0.65 0.83 0.99 1.09
Static pressure of 50 Pa H 0.21 0.29 0.35 0.41 0.52 0.74 0.85 1.03 1.27
Sound dB(A) Static pressure of 12 Pa H 34.5 34.5 37.5 41.0 45.0 44.5 48.0 49.0 52.0
Static pressure of 30 Pa H 37.0 40.0 42.5 44.0 45.5 46.5 49.5 49.5 53.0
Static pressure of 50 Pa H 41.0 43.0 45.0 46.0 47.5 48.0 50.0 51.0 53.5
Water flow (m3/h) 0.32 0.51 0.67 0.80 0.88 1.31 1.47 1.81 2.01
Water resistance (cooling) (kPa) 5 14 26 36 18 40 28 40 34
Water resistance (heating) (kPa) 4 12 21 30 14 34 23 34 28
Coil Type Mechanically expanded quality copper tubes specially designed for air conditioners with shutter-type hyperbolic aluminum fins
Working pressure 1.6MPa
Test pressure Airtightness test under pressurized water: 3.3 MPa
Fan Type Forward-pitched multi-wing centrifugal fan with double-suction impellers made from zinc-plated steel plates
bigPhoto
 Mr. Rocky

Tel: 86-769-83660888
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

EuroKlimat Air Conditioning Refrigeration Company [China (Mainland)]


Business Type:Manufacturer
City: Dongguan
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (197)